Перевод: со всех языков на все языки

со всех языков на все языки

multi-voltage power solution

  • 1 multi-voltage power solution

    Англо-русский словарь нормативно-технической терминологии > multi-voltage power solution

  • 2 система на несколько напряжений

    Русско-английский словарь нормативно-технической терминологии > система на несколько напряжений

  • 3 параллельная система ИБП

    1. parallel UPS system

     

    параллельная система ИБП
    -

    [Интент]

    Parallel Operation: The system shall have the option to install up to four (4) UPSs in parallel configuration for redundancy or capacity.
    1. The parallel UPS system shall be of the same design, voltage, and frequency. UPS modules of different size ratings shall be permitted to be paralleled together for purposes of increased capacity or UPS module redundancy. The UPSs in the parallel configuration shall not be required to have the same load capacity rating.
    2. Parallel Capacity: With N+0 system-level redundancy, up to 2MW of load can be supported by the system.
    3. Parallel Redundancy: With N+1 system-level redundancy, up to 1.5MW of load can be supported by the system, and only the UPS being replaced must be isolated from the source (bypass operation is not required for the entire system during the UPS replacement procedure).
    4. Output control: A load sharing circuit shall be incorporated into the parallel control circuits to ensure that under no-load conditions, no circulating current exists between modules. This feature also allows each UPS to share equal amounts of the total critical load bus. The output voltage, output frequency, output phase angle, and output impedance of each module shall operate in uniformity to ensure correct load sharing. This control function shall not require any additional footprint and shall be an integral function of each UPS. The static bypass switches shall be connected in parallel.
    5. Parallel System Controls: To avoid single points of failure, the UPS system shall have no single dedicated control system designed to control the operation of the parallel UPS system. Control of and direction of parallel UPSs shall take place via a master/slave relationship, where the first UPS to receive logic power asserts itself as a master. In the event of a master failure, a slave UPS shall take the role of master and assume the responsibility of the previous master UPS. Regardless of which UPS is master or slave, user changes to the system status, such as request for bypass, can be done from any UPS connected to the bus and all UPS on the bus shall transfer in simultaneously.
    6. Communication: Communication between modules shall be connected so that the removal of any single cable shall not jeopardize the integrity of the parallel communication system. Load sharing communications shall be galvanically isolated for purposes of fault tolerance between UPS modules. A UPS module's influence over load sharing shall be inhibited in any mode where the UPS inverter is not supporting its output bus. Transfers to and from bypass can be initiated from any online UPS in the system.
    7. Display: Each UPS multi-color LCD touch screen user interface shall be capable of using an active touch screen mimic bus to show the quantity of UPS(s) connected to the critical bus, as well as the general status of each UPS, such as circuit breaker status information. Any touchscreen display shall support the configuration of the [entire parallel] system and shall provide event and alarm data for all UPSs in the parallel configuration. A Virtual Display Application shall be available for download to the customer’s computer and shalll support remote monitoring of a complete system with up to 4 UPSs in parallel.
    8. Battery runtime: Each UPS must have its own battery solution. The battery solution for the entire system can be a combination of standard and third-party batteries, but each UPS must use only one battery solution – either standard or third-party batteries.
    9. Switchgear: A custom switchgear option shall be required for parallel operation.

    [Schneider Electric]

    Тематики

    EN

    Русско-английский словарь нормативно-технической терминологии > параллельная система ИБП

  • 4 parallel UPS system

    1. параллельная система ИБП

     

    параллельная система ИБП
    -

    [Интент]

    Parallel Operation: The system shall have the option to install up to four (4) UPSs in parallel configuration for redundancy or capacity.
    1. The parallel UPS system shall be of the same design, voltage, and frequency. UPS modules of different size ratings shall be permitted to be paralleled together for purposes of increased capacity or UPS module redundancy. The UPSs in the parallel configuration shall not be required to have the same load capacity rating.
    2. Parallel Capacity: With N+0 system-level redundancy, up to 2MW of load can be supported by the system.
    3. Parallel Redundancy: With N+1 system-level redundancy, up to 1.5MW of load can be supported by the system, and only the UPS being replaced must be isolated from the source (bypass operation is not required for the entire system during the UPS replacement procedure).
    4. Output control: A load sharing circuit shall be incorporated into the parallel control circuits to ensure that under no-load conditions, no circulating current exists between modules. This feature also allows each UPS to share equal amounts of the total critical load bus. The output voltage, output frequency, output phase angle, and output impedance of each module shall operate in uniformity to ensure correct load sharing. This control function shall not require any additional footprint and shall be an integral function of each UPS. The static bypass switches shall be connected in parallel.
    5. Parallel System Controls: To avoid single points of failure, the UPS system shall have no single dedicated control system designed to control the operation of the parallel UPS system. Control of and direction of parallel UPSs shall take place via a master/slave relationship, where the first UPS to receive logic power asserts itself as a master. In the event of a master failure, a slave UPS shall take the role of master and assume the responsibility of the previous master UPS. Regardless of which UPS is master or slave, user changes to the system status, such as request for bypass, can be done from any UPS connected to the bus and all UPS on the bus shall transfer in simultaneously.
    6. Communication: Communication between modules shall be connected so that the removal of any single cable shall not jeopardize the integrity of the parallel communication system. Load sharing communications shall be galvanically isolated for purposes of fault tolerance between UPS modules. A UPS module's influence over load sharing shall be inhibited in any mode where the UPS inverter is not supporting its output bus. Transfers to and from bypass can be initiated from any online UPS in the system.
    7. Display: Each UPS multi-color LCD touch screen user interface shall be capable of using an active touch screen mimic bus to show the quantity of UPS(s) connected to the critical bus, as well as the general status of each UPS, such as circuit breaker status information. Any touchscreen display shall support the configuration of the [entire parallel] system and shall provide event and alarm data for all UPSs in the parallel configuration. A Virtual Display Application shall be available for download to the customer’s computer and shalll support remote monitoring of a complete system with up to 4 UPSs in parallel.
    8. Battery runtime: Each UPS must have its own battery solution. The battery solution for the entire system can be a combination of standard and third-party batteries, but each UPS must use only one battery solution – either standard or third-party batteries.
    9. Switchgear: A custom switchgear option shall be required for parallel operation.

    [Schneider Electric]

    Тематики

    EN

    Англо-русский словарь нормативно-технической терминологии > parallel UPS system

См. также в других словарях:

  • Power dividers and directional couplers — A 10 dB 1.7–2.2 GHz directional coupler. From left to right: input, coupled, isolated (terminated with a load), and transmitted port …   Wikipedia

  • Common Power Format — The Si2 Common Power Format, or CPF is a file format for specifying power saving techniques early in the design process. In the design of integrated circuits, saving power is a primary goal, and designers are forced to use sophisticated… …   Wikipedia

  • Uninterruptible power supply — A small free standing UPS …   Wikipedia

  • Optimisation des performances des architectures multi-cœurs — Un microprocesseur multi cœur (multi core en anglais) est un processeur possédant plusieurs cœurs physiques. Depuis l’arrivée des premiers microprocesseurs double cœurs en 2005, le nombre de cœurs ne cesse d’augmenter dans l’objectif d’améliorer… …   Wikipédia en Français

  • Fusion power — The Sun is a natural fusion reactor. Fusion power is the power generated by nuclear fusion processes. In fusion reactions two light atomic nuclei fuse together to form a heavier nucleus (in contrast with fission power). In doing so they release a …   Wikipedia

  • Nuclear power — Atomic Power redirects here. For the film, see Atomic Power (film). This article is about the power source. For nation states that are nuclear powers, see List of states with nuclear weapons …   Wikipedia

  • система на несколько напряжений — [Интент] Тематики электротехника, основные понятия Синонимы система электропитания на несколько напряжений EN multi voltage power solution …   Справочник технического переводчика

  • Electric double-layer capacitor — Maxwell Technologies MC and BC series supercapacitors (up to 3000 farad capacitance) An electric double layer capacitor (EDLC), also known as supercapacitor, supercondenser, electrochemical double layer capacitor, or ultracapacitor, is an… …   Wikipedia

  • Charging station — Level 2 charging station for the Nissan Leaf …   Wikipedia

  • Tissue engineering — Principle of tissue engineering Tissue engineering was once categorized as a sub field of bio materials, but having grown in scope and importance it can be considered as a field in its own right. It is the use of a combination of cells,… …   Wikipedia

  • Electric motor — For other kinds of motors, see motor (disambiguation). For a railroad electric engine, see electric locomotive. Various electric motors. A 9 volt PP3 transistor battery is in the center foreground for size comparison. An electric motor converts… …   Wikipedia

Поделиться ссылкой на выделенное

Прямая ссылка:
Нажмите правой клавишей мыши и выберите «Копировать ссылку»